ERCOT to blame for Texas blackouts, not renewables or fossil fuels

February's deep freeze not only sunk much of Texas into a dark, powerless, snow-riddled period, it sapped the energy grid that affected millions across the state.

At the McKelvey School of Engineering at Washington University in St. Louis, the situation and the fallout that followed - the rolling or lasting blackouts, national attention, the termination of the energy group's CEO - prompted Richard Axelbaum, Stifel & & Quinette Jens Professor of Environmental Engineering Science, and Phillip Irace, PhD candidate and NSF Graduate Student Fellow, to take a closer look.

This is an extended version of an analysis first published by Real Clear Energy.

In mid-February, Texans were plunged into a period of freezing cold and snow, causing an unprecedented demand for electricity. Alas, the Texas electric grid - operated largely by the Electric Reliability Council of Texas (ERCOT) - was unable to meet that demand, plunging over 4 million Texans into the cold darkness. The electricity shortage was not caused by frozen wind turbines or natural gas plants, but rather ERCOT mismanagement and poor planning.

What happened in February? To appreciate what transpired, one must understand that to ensure a stable electrical grid, the total supply from all energy sources must equal demand instantaneously. As the cold spell hit on Feb. 9, the demand for electricity immediately began to rise (Figure 1). Unfortunately, as temperatures began to drop, the wind (blue curve) died down, and Texas was forced to meet rising demand by ramping up its natural gas power plants (green curve).

Figure 1. Source: https://www.eia.gov

In the late hours of Valentine's Day, as temperatures plummeted to their lowest, the dispatchable energy sources (coal, natural gas, and nuclear) were operating near maximum capacity. This is a very dangerous condition, like running your car with the pedal smashed to the floor. Eventually, something will give out. And soon, it did. A number of plants went offline, which is not an unusual occurrence for a grid the size of ERCOT's. However, with no reserve power to make up for the outages, the entire grid became unstable, forcing many more plants to shut down as well. Technically, what happened was the reduction in energy supply, without any reserve power to make up for it, caused the frequency in the grid to plummet. A rapid drop in frequency is catastrophic for the grid. Texas was only minutes away from a catastrophic failure that could have left millions more in the dark for days, or even weeks. To prevent that, ERCOT was forced to introduce a series of rolling blackouts.

During a typical winter, Texas has no difficulty meeting electricity demand. In the same month of 2019 (Figure 2), ERCOT was able to instantaneously meet demand for the entire month, even though there were a number of times when the output from wind power was nearly zero.

Figure 2. Source: https://www.eia.gov

February 2021 was different. The cold snap was an atypically extreme weather phenomenon, which caused the electricity demand to skyrocket. However, this isn't the first time Texas has experienced such low temperatures. The temperatures were lower in 1989 and 1983. Not to mention, there were 20 nights of below freezing temperatures in Houston in 1978. This year's temperatures were certainly within the expectations of ERCOT. Moreover, in the past three years, Texas has increased its total electric capacity. So why the sudden shortage? It seemed like Texas was prepared. And if it was, why was the ERCOT CEO abruptly let go? The question asked from a political perspective: Wasn't the real problem wind (if you are conservative), fossil fuels (if you are liberal) or the weather (if you are ERCOT)?

But the problem wasn't wind, fossil fuels, nor the extreme weather. The problem was ERCOT and its inability to acknowledge, and plan for, the limitations of wind and solar amidst extreme weather events. ERCOT certainly had plenty of warning in past years that wind dies down in times of cold weather.

The data from February 2019 (Figure 2) illustrates that ERCOT officials knew what to expect from wind in the winter. Wind power (blue curve) supplied nearly 20,000 MW at times, but almost nothing at other times. In fact, it was often during times of peak demand when the wind was virtually nonexistent. The senior management at ERCOT knew they could not rely on wind in the winter. Nonetheless, ERCOT continued to build wind energy capacity, but more importantly, in the process, they prematurely decommissioned coal plants (Figure 3).

Figure 3. Source: http://www.ercot.com

To better understand the event of Feb. 15 (Figure 4), consider the combined winter installed capacity from all "dispatchable sources" - i.e., coal, natural gas and nuclear (horizontal dashed black line). This quantity represents how much electricity can be produced if all the coal, natural gas and nuclear plants are running at their maximum installed capacity. Expecting more than 90% of this to be available is unrealistic due to occasional outages and maintenance. Thus, the available capacity was more like 60,000 MW, which was reached on the night of Feb. 14.

Figure 4. Source: http://www.eia.gov/, http://www.ercot.com/ and https://www.timeanddate.com

In the early morning hours of Feb. 15, about 1:30 a.m., a number of smaller plants went offline within about 10 minutes of each other, as listed in Table 1 (below). Combined, they amounted to about 2.4GW, which for a grid with enough reserve power would have been a manageable event. But, with ERCOT already running near maximum capacity with no reserve, this quickly dropped the frequency of the grid (Figure 5). The frequency of the grid must be maintained at 60 Hz in order to maintain stability. Rapid variations in frequency is a crisis, and this event forced ERCOT to immediately call for load-shedding by inducing rolling blackouts. But the damage was already done. With no reserve power to rely on, and a rapid drop in frequency, the grid was unstable, and this led to more plants tripping offline. To avoid a total collapse of the grid, ERCOT was forced to induce many more blackouts, and this plunged Texas into a cold darkness.

Table 1. Information includes only natural-gas power plants. No coal or nuclear plants went out during this time. Source: ERCOT letter to Texas legislature
Figure 5. Source: ERCOT Board of Directors meeting Feb. 24.

Some want to argue that this event occurred because natural gas lines froze. While at some point in the night, likely much after this event, some lines may have frozen, Table 1 shows that this was not the root cause of the problem. Natural-gas power plants in five different counties went offline at nearly the same time. The temperatures in these counties were much different, as was the construction of the gas lines. The odds of them all freezing at the same time is essentially zero. While the exact cause of these simultaneous outages may never be revealed, when the frequency of the grid drops, this leads to an instability of the grid that can force many more outages. Without any reserve capacity available to quickly ramp up when these plants went offline, the condition was dire.

Outages of this magnitude shown in Table 1 typically occur without a major incident, so why wasn't ERCOT prepared with more reserve capacity? You might say they tried to be, because they did increase the total grid capacity (Figure 3). But they did this by installing more intermittent wind energy. Wind energy is capable of producing over 21,000 MW in Texas (as seen in Figure 1), but wind is not always available in winter. During February 2021, energy from wind steadily decreased, leaving the other energy sources to be strained to the max in a futile attempt to meet demand, and, ultimately, they failed.

/Public Release. This material from the originating organization/author(s) might be of the point-in-time nature, and edited for clarity, style and length. Mirage.News does not take institutional positions or sides, and all views, positions, and conclusions expressed herein are solely those of the author(s).View in full here.